Detailed Thermal Evaluation of Brazed Plate Heat Exchanger Using Infrared Thermography
Abstract: Infrared thermography of brazed plate heat exchangers for evaporators and condensers recently was used to quantify maldistribution. With the knowledge of the secondary fluids heat transfer coefficient and a given secondary fluids distribution, the local heat transfer coefficient of the primary fluid (refrigerant) and its distribution to the channels can be calculated. A sensitivity analysis shows ± 10 % difference of the surface temperature to the wall center temperature at the expected ratios of heat transfer coefficients. The method is presented in this paper using an exemplary infrared picture.
- Location
-
Deutsche Nationalbibliothek Frankfurt am Main
- Extent
-
Online-Ressource
- Language
-
Englisch
- Bibliographic citation
-
Detailed Thermal Evaluation of Brazed Plate Heat Exchanger Using Infrared Thermography ; day:30 ; month:03 ; year:2023 ; extent:9
Chemie - Ingenieur - Technik ; (30.03.2023) (gesamt 9)
- Creator
-
Will, Torsten
Schnabel, Lena
Köhler, Jürgen
- DOI
-
10.1002/cite.202200215
- URN
-
urn:nbn:de:101:1-2023033015234193235729
- Rights
-
Open Access; Der Zugriff auf das Objekt ist unbeschränkt möglich.
- Last update
-
14.08.2025, 10:49 AM CEST
Data provider
Deutsche Nationalbibliothek. If you have any questions about the object, please contact the data provider.
Associated
- Will, Torsten
- Schnabel, Lena
- Köhler, Jürgen